Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
EMC emission of interference
per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
EMC immunity to interference
per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;
EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Mounting position
Horizontal left, horizontal up, vertical top and vertical bottom
Operating altitude
without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Permissible H₂S contaminant concentration
10 ppm
Permissible SO₂ contaminant concentration
25 ppm
Pollution degree
2 per IEC 61131-2
Protection type
IP20
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Relative humidity (without condensation)
95 %
Shock resistance
per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
Vibration resistance
per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373