Unknown: Implicit conversion from float 176.5 to int loses precision in /var/www/mikroprylad/mikroprylad.com.ua/system/library/image.php on line 268855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A
Short description:WAGO's plug-in current transformers for billing measurement (855 Series) are inductive, single-conductor current transformers. Due to the measurement principle used, these current transformers are exclu...
The nearest branch addresses can be viewed on the map.
from
150.00 грн.
Pickup (Kyiv)
For free
Description 855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A
Short description: WAGO's plug-in current transformers for billing measurement (855 Series) are inductive, single-conductor current transformers. Due to the measurement principle used, these current transformers are exclusively designed for AC network applications. These plug-in current transformers comply with the conformity assessment procedure (module D) and can be used for billing. Features:
Screwless CAGE CLAMP® connection technology
Several mounting options available
Vibration- and shock-resistant
High mechanical retention forces
High current-carrying capacity
Continuous overload of 120 % the nominal primary current
Low-voltage current transformer for operating voltages up to max. 1.2 kV
For 690 V power networks
Accessories: 879-3040; Energy Meter; with Push-in CAGE CLAMP® and lever; transformer connection (2PUCT)
Main attributes 855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A
Connection 1
Connection technologyCAGE CLAMP®
Fine-stranded conductor0.08 … 4 mm² / 28 … 12 AWG
Solid conductor0.08 … 4 mm² / 28 … 12 AWG
Strip length9 … 10 mm
Environmental requirements
Ambient temperature (operation)-5 … +50 °C
Ambient temperature (storage)-25 … +70 °C
Operating altitude (max.)1000 m
Input
Measured variableCurrent
Input – current transformer
Overcurrent limiting factorFS5 / FS10 (type dependent; see type plate inscription)
Primary rated current250 A
Rated continuous thermal current IₜₕAC 1.2 x IN
Rated frequency50 … 60 Hz
Rated short-time thermal current Iₜₕ60 x IN / 1 s (max. 100 kA / 1 s)
Material data
Insulation classE
Weight280 g
Measurement error
Accuracy class0.5
Mechanical data
Mounting typeMounting on DIN-rail via DIN-rail adapter
Output – current transformer
Rated power Sᵣ2.5 VA
Secondary rated current5 A
Physical data
Depth52 mm
Height91.15 mm
Width70 mm
Safety and protection
Highest voltage for equipment UₘAC 1.2 kVrms
Test voltageAC 6 kV; 50 Hz; 1 min
Standards and specifications
Conformity markingCE
Standards/specificationsEN 61869-2
Reviews about 855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A
0
0
1
0%
2
0%
3
0%
4
0%
5
0%
There are no reviews for this product.
Write a review
Questions and Answers (FAQ) 855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A
There are no questions about this product.
Ask a Question
855-405/250-209 Plug-in current transformer;Primary rated current: 250 A;Secondary rated current: 5 A